Also known as
Open Phase Detected

This is an inverter warning, shown as warning event code 4, that reports an open AC phase on the grid side. It is a warning-class event in the inverter event list, separate from the critical events such as an AC contactor failure. To confirm it, measure the AC voltage on each phase with a CAT III multimeter. If one phase has no voltage, check all AC fuses and breakers and look for damage on the AC conductors. If the meter shows no phase loss, the warning may not reflect a real field condition, and the manual says to contact the manufacturer's technical support.

<!-- review notes

Signals

Monitoring channels where this signature appears, named by SunSpec model point.

PointUnitPattern
model_103.PhVphAVone AC phase voltage missing or abnormal compared with the other phases