Low insulation resistance alarm

ID
meas:low-insulation-resistance-alarm
IRI
https://solarlattice.org/kb/meas/low-insulation-resistance-alarm
Status
active
Also known as
IsolationErr, Insulation resistance low, low insulation fault, PV ISO-PRO 01/02, meas:low-ground-fault-resistance, Low ground fault resistance

The inverter raises a protection alarm when it detects low DC insulation resistance between the PV circuit and earth ground. It often shows up after rain or in the early morning when modules are wet with dew, and the inverter may switch off when the resistance falls below its limit. Bad module insulation cannot be seen by eye. Only an insulation resistance measurement confirms it, and testing in humid or wet conditions works better than testing dry. To find the faulted string, isolate all strings, then add them back one at a time and restart the inverter until the alarm returns. Then trace that string for leakage to ground. Note the weather when the alarm occurs. If a dry measurement looks normal, measure again in the same weather that triggered the alarm and check the cables physically. Broken module glass can cause insulation faults and moisture ingress. Aged backsheets can crack and lose their insulating properties. If a voltage measurement does not clearly show a ground fault, an insulation resistance measurement gives more exact results.

<!-- review notes

Signals

Monitoring channels where this signature appears, named by SunSpec model point.

PointUnitPattern
model_103.WWinverter stops exporting while the insulation alarm is active
model_302.POAIW-PER-M2normal morning irradiance while the inverter stays offline
model_307.RHPERCENThigh humidity or dew at the time the inverter fails to start