Islanding breaker open flag
This signature is a read-only boolean status point that reports the position of the islanding breaker on the site controller. A value of 1 means the islanding breaker is closed and the system is connected to the grid. A value of 0 means the islanding breaker is open and the system is running off-grid, which is the pattern to look for when islanding is reported. Over Modbus, the point is read from register 29025 as a single int16 value. An open breaker can also come from a deliberate command: a user can write the Intentional Island point to open the islanding breaker. Before treating an off-grid reading as unexpected, check the Intentional Island setpoint and its feedback point.