High inverter internal temperature

ID
meas:inverter-temperature-high
IRI
https://solarlattice.org/kb/meas/inverter-temperature-high
Status
active
Also known as
Internal Air Temperature, OverTemp, OV-TEM, Critical Over Temperature, Temp derating, temperature derating

Inverters report an internal air temperature value, and you can read it on the display or in the monitoring data. When the internal or ambient temperature gets too high, the inverter cuts its output power. Monitoring may show this as a temperature derating message or a derating state. Some manuals say derating starts at about 45 °C. One model reduces output in a straight line up to 60 °C and then shuts down to protect itself. If the temperature keeps rising, the inverter may stop producing power completely and show an overtemperature protection alarm or a critical overtemperature fault. Inverters do not always report the power reduction. To confirm derating, check a plot of power against irradiance. Common causes are poor installation or spacing, fan failure, dust or debris blocking cooling or vents, direct sunlight, high ambient temperature and wrong inverter settings. An abnormal temperature reading can also come from a poorly contacting internal temperature sensor, so compare the displayed value with the actual conditions before blaming overheating.