ID
meas:clock-battery-voltage-low
IRI
https://solarlattice.org/kb/meas/clock-battery-voltage-low
Status
active
Also known as
Batt. Low, Battery Low, LOWBAT, BATT

Some meters report the real-time clock battery voltage as a diagnostic value in volts. The value refreshes about once per second. A built-in self-test measures the clock battery voltage. When the voltage drops below the 2.3 V limit, the self-test raises a warning and pulses the alarm output, and the meter keeps running. A status bit called LOWBAT flags a low real-time clock battery warning. On some inverters, a backup battery voltage that is too low shows as warning W012 Batt. Low, with a flashing yellow LED. To confirm it, check that the date and time are set correctly. Then switch the inverter fully off on both the AC and DC sides, wait a few minutes and restart it. If the date and time have reset to 01/01/2000, the battery is no longer keeping the clock. If the clock does not hold, replace the battery with the inverter isolated on both the AC and DC sides, and keep the battery polarity correct.