Analog setpoint signal low

ID
meas:analog-setpoint-signal-low
IRI
https://solarlattice.org/kb/meas/analog-setpoint-signal-low
Status
active
Also known as
AnInFail

On SMA central inverters the reactive power setpoint status reads AnInFail when an analog-input mode such as VArCnstNomAnIn or PFCnstAnIn is selected and the analog input measures less than 2 mA. Analog setpoints reach the Cluster Controller as current signals from 0 mA to 20 mA, used for active power limitation and the reactive power setpoint. The Cluster Controller treats analog input signals as valid up to 21 mA, so a slight overload can be used to reach the maximum setpoint. An invalid input status is only recorded as a fault after the configured failure tolerance time has passed. If the display shows no current signal for the analog signal source or sensor, the source or sensor is probably not connected correctly. The recommended first step is to check that the cable is properly connected to the analog input.