FailureMode
Precharge circuit failure
- ID
fm:precharge-circuit-failure
- IRI
https://solarlattice.org/kb/fm/precharge-circuit-failure
- Status
- active
- Also known as
- Event 6456, Error 6456, Precharging Circuit Defective
On SMA Sunny Central inverters, event 6456 means the circuit that pre-charges the DC link is defective. In the data log it can show up as a mismatch: the frequency of the AC voltage metering does not match the grid AC voltage. The manual lists the inverter behavior for this event as W. First check whether the inverter has the Q at night function and whether the QoDEna parameter is enabled. Next, check the pre-charging input fuses and the pre-charging feedback signal at SC20CONT terminals X14-8 and X14-9. If those checks find nothing wrong, contact SMA Service.
<!-- review notes
- sentence 4: support check: partial - u1 asks about the Q at night function and QoDEna, but its flow is garbled (a 'No' branch asks about QoDEna), so 'first check whether it has the function and whether QoDEna is enabled' is only roughly stated.
-->
Claims
affects
c1 verified · fact
DC link precharge circuit
SMA Sunny Central event 6456 reports the DC link pre-charging circuit as defective.
verified by: review-workflowverified on: 2026-10-23
c2 drafted · lead
Inverter
Reported for Sunny Central central inverters (SC-XXX-CP-10, SC-XXX-JP, SC CP XT).
review note: support check: partial - The passages name the Sunny Central and list SC-XXX-CP-10 and SC-XXX-JP, but SC CP XT is not mentioned.
presents_as
c3 verified · fact
AC voltage measurement mismatch
In the data log, the frequency of the AC voltage metering does not match the grid AC voltage.
verified by: review-workflowverified on: 2026-10-23
detected_by
c4 drafted · lead
Fuse inspection
Check the pre-charging input fuses and the pre-charging feedback signal at SC20CONT terminals X14-8 and X14-9.
c5 verified · fact
Inverter settings review
First check whether the inverter has the Q at night function and whether the QoDEna parameter is enabled.
verified by: review-workflowverified on: 2026-10-23
mitigated_by
c6 verified · fact
Contact manufacturer service
Contact SMA Service if the fuses and feedback check out OK, or straight away according to the operating manual.
verified by: review-workflowverified on: 2026-10-23