c1 verified · fact Load-side connection
The busbar rating methods apply to connections made on the load side of the service disconnecting means.
- NEC2017 705 [code/standard]
sec=h9h=6de44b94103f
verified by: review-workflowverified on: 2026-10-24
The 120% busbar rule is an NEC method for load-side PV connections. It adds 125 percent of the source output circuit current to the rating of the breaker protecting the busbar, and that sum may reach up to 120 percent of the busbar ampacity. It only applies when the utility and the inverter feed the busbar from opposite ends, the busbar serves loads, and the busbar is sized for those loads under Article 220. A permanent warning label must be placed next to the back-fed breaker telling people not to relocate it. Moving that breaker could load the busbar beyond its rating. For example, a 200 A busbar fed by a 200 A main breaker allows an inverter output current of up to 32 A. In field terms, the maximum solar breaker is the busbar rating times 1.2 minus the main breaker rating, and the solar breaker itself is sized at 1.25 times the inverter's maximum continuous current. If that is not enough, the options are derating the main breaker, a line side tap, or a main panel upgrade. A Temporary Interim Amendment, carried into the 2017 NEC, lets the same 120 percent limit apply to a PV breaker at either end of a center-fed panelboard in a dwelling. Other busbar methods include the 100 percent sum rule, the sum-of-breakers rule used for AC combiner panels, and designs done under engineering supervision.
<!-- review notes
related_toc1 verified · fact Load-side connection
The busbar rating methods apply to connections made on the load side of the service disconnecting means.
sec=h9 h=6de44b94103fverified by: review-workflowverified on: 2026-10-24
The limit is set as a percentage of the busbar ampacity.
sec=h25 h=c63742cb1b49sec=h9 h=6de44b94103fsec=h159 h=9edad9ff2e02c3 drafted · lead Overcurrent protection
The rating of the overcurrent device protecting the busbar is part of the sum.
sec=h25 h=c63742cb1b49sec=h9 h=6de44b94103fc4 drafted · lead Supply-side connection
A line side tap is listed as an option when the 120% rule does not leave enough room for the solar breaker.
sec=h2 h=304eea485e46related_to c2