240 V high-leg delta service

ID
arch:high-leg-delta-240v
IRI
https://solarlattice.org/kb/arch/high-leg-delta-240v
Status
active
Also known as
high-leg delta, stinger leg, 240/120 V delta, Hi-Leg Delta, Delta Hi Leg, Stinger leg AC Grid, Three phase high leg delta, 240V High-leg Delta
Category
Grid service

High-leg delta is an older service type, found mainly in rural areas. It was a cheap way to deliver 240 V three-phase plus 240 V or 120 V single-phase from one pole-mounted transformer. On the Solis S6-GC-30K-LV-US, the high side goes on the L2 or B phase. That phase is shown with the larger conductor at the AC input. The Solis S6-GC-30K-LV-US can connect to a 240 V high-leg delta service. First update it to HMI software C701 and DSP software 5906, then select the UL-240L grid standard. The Fronius Symo and Symo Advanced 10.0-3 and 12.0-3 208-240 models have a Hi-Leg Delta setup (HI1). A neutral conductor is required. Enphase IQ commercial microinverters cannot connect directly to a 240 V high-leg delta service. They need a transformer with a 208/120 V wye secondary, chosen by the installer according to the NEC and local code. Eaton makes 120/240 V high-leg delta surge protective devices with their own wiring diagram. Their protection modes include high leg to neutral, high leg to ground and high leg to line.