Corner-grounded delta service

ID
arch:corner-grounded-delta
IRI
https://solarlattice.org/kb/arch/corner-grounded-delta
Status
active
Also known as
corner grounded delta, Corner-Grounded Delta System, Delta Corner Grounded, corner grounded Delta grid configuration
Category
Grid service

A corner-grounded delta is a three-phase delta system with one phase conductor, usually the B-phase, tied to ground to hold all voltages to ground steady. The voltages from each phase to ground are not equal, so this arrangement does not suit single-phase loads. Because one phase conductor is grounded, it can be mistaken for an ungrounded phase. Clear phase identification is needed to avoid shock. Like other solidly grounded systems, a ground fault draws a large fault current, and that fault has to be cleared quickly. This arrangement is no longer common and is found in only a few existing facilities. Better options are available for new installations. On 480 V delta commercial services, co-located loads that cause repeated line-to-ground faults can turn the service into a corner-grounded delta in effect. In that case the PV system has to be isolated from the fault source to protect the inverters from excessive line-to-ground voltage. Some residential inverters list 208 V, 220 V and 240 V corner-grounded delta among their selectable grid configurations.